The Polytron 8100 EC is Draeger’s top of the line explosion proof transmitter for the detection of toxic gases or oxygen. It uses a high performance plug and play electrochemical DragerSensor® to detect a specific gas. Besides a 3 wire 4 to 20 mA analogue output with relays, it also offers Modbus and Fieldbus protocol making it compatible with most control systems.
• Durable, intelligent and sensitive – the DraegerSensor
• Easy device management via digital communication
• Same design, same operating principle (Polytron 8100 belongs to the Polytron 8000 series)
• Three relays for controlling external equipment
• Safe, robust housing for every application
• Remote sensor option does not require conduit
• More functions through dongles
• Oil refineries/mining/OnShore/Off Shore /Water treatment Plant
• Normal measurment possible with 4-20mA , Hart and optional Relay
• Measuement of Toxic Gases inside the Duct ( Remote installation up to 30 meters Available)
• Hazardous area Application (zone 1,Zone2)
• Contionous monitoring of Oxygen,H2S, Confined Space Installation to monitor
• Remote installation with relay options.
Type
Explosion proof / flameproof enclosed transmitter (“d”) or combined with increased safety (“d/e”)
Gases and Ranges
Toxic gases and oxygen, dependent on the sensor used
Measuring ranges
Customized adjustment
Display
Backlit graphic LCD; 3 Status LEDs (green/yellow/red)
Signal output analogue
Normal operation – 4 to 20 mA, 3- or 4-wire, sink or source
Maintenance – Constant 3.4 mA or 4 mA
Fault – < 1.2 mA
Signal output digital
HART® w/ 3- or 4-wire, PROFIBUS® PA, FOUNDATION fieldbus™ H1 and Modbus RTU w/ 4-wire
Power supply
10 to 30 V DC
Relay specification (option)
2 alarm relays and 1 fault relay, SPDT 5 A @ 230 VAC , 5 A @ 30 VDC, resistance-bound
Temperature
-40 to 65 °C (-40 to 149 °F) without relay , -40 to 65 °C (-40 to 149 °F) with relay
Pressure
20.7 to 38.4 inch Hg / 700 to 1,300 mbar
Humidity
0 to 100 % r. h., non-condensing
Transmitter housing
Epoxy coated copper-free aluminium or stainless steel SS316 L
Sensor housing
Polyamide
Enclosure protection type
NEMA 4X & 7, IP65/66/67
Cable entry point
3/4″ NPT threaded holes or M20 cable gland
Dimensions (H x W x D)
w/o docking station – 11.0″ x 5.9″ x 5.1″ / 280 x 150 x 130 mm
w/ docking station – 11.0″ x 7.1″ x 7.5″ / 280 x 180 x 190 mm
Weight, approx
6.6 lbs / 3.0 kg to 14.3 lbs / 6.5 kg
Approvals
UL, CSA, IECEx, ATEX, CE markings, SIL 2 certified by TUEV Sued,
The Draeger Polytron 8200 CAT is an advanced explosion proof transmitter for the detection of flammable gases in the lower explosion limit (LEL). It uses a catalytic bead DraegerSensor Ex … DD, which will detect most flammable gases and vapors. Besides a 3 wire 4 to 20 mA analog output with relays, it also offers Modbus and Fieldbus protocols making it compatible with most control systems.
• Fast and stable – the DrägerSensor® Ex
• Easy device management via digital communication
• Same design, same operating principle
• Three relays for controlling external equipment
• Safe, robust housing for every application
• Make the impossible possible with the remote sensor
• Data logger
• Oil refineries/mining/OnShore/Off Shore /Water treatment Plant
• Continous monitoring of Hydrocarbon , Hydrogen Flammable Gases using Catalytic technology
• Measuement of Flammable inside the Duct upto 150degc ( Remote installation up to 30 meters Available)
• Hazardous area Application (zone 1,Zone2)
• Continous monitoring of Hygrogen in battery rooms
Type
Explosion-proof / flameproof enclosed transmitter (“d”) or combined with increased safety (“d/e”)
Gases
flammable gases and vapours
Measuring ranges
DQ 0 to 100 % LEL , LC 0 to 10 % LEL
Display
Backlit 4 digit LCD; 3 Status LEDs (green/yellow/red)
Accuracy/repeatability
≤ 1 % LEL
Response time
< 7 seconds to < 13 seconds
Signal output analogue
Normal operation – 4 to 20 mA, 3- or 4-wire, sink or source
Maintenance – Constant 3.4 mA or 4 mA ±1 mA 1 Hz modulation;(adjustable)
Fault – < 1.2 mA
Signal output digital
HART® w/ 3- or 4-wire, PROFIBUS® PA, FOUNDATION fieldbus™ H1 and Modbus RTU w/ 4-wire
Power supply
10 to 30 V DC
Relay specification (option)
2 alarm relays and 1 fault relay, single-pole two-way contact 5 A @ 230 VAC, 5 A @ 30 VDC, resistance-bound
Temperatur
-40 to 80 °C (-40 to 176 °F)
Pressure
20.7 to 38.4 inch Hg / 700 to 1,300 mbar
Humidity
0 to 100 % RH, non-condensing
Transmitter housing
Epoxy coated copper-free aluminum or SS316 L stainless steel
The Dräger Polytron® 8310 IR is an advanced explosion proof transmitter for the detection of combustible gases in the lower explosion limit (LEL). It uses an infrared DrägerSensor® IR that can be configured for methane, propane or ethylene. Besides a 3 wire 4 to 20 mA analogue output with relays, it also offers Modbus and Fieldbus protocols making it compatible with most control systems.
• Poison-resistant and fail-safe – the DrägerSensor® IR
• Easy device management via digital communication
• Same design, same operating principle
• Three relays for controlling external equipment
• Safe, robust housing for every application
• Make the impossible possible with the remote sensor
• Data logger
For the detection of combustible gases in the lower explosion limit (LEL). It uses an infrared DrägerSensor® IR that can be configured for methane, propane or ethylene. Besides a 3 wire 4 to 20 mA analogue output with relays, it also offers Modbus and Fieldbus protocols making it compatible with most control systems. Long life optics result in lower maintenance costs compared to pellistors. IR technology is inherently fail-safe, meaning no unrevealed failures.
Type
Explosion proof / flameproof enclosed transmitter (“d”) or combined with increased safety (“d/e”)
Gases
Flammable gases and vapours
Measuring range
0 to 20 … 100 % LEL
Display
Backlit graphic LCD; 3 Status LEDs (green/yellow/red)
Signal output analogue
4 to 20 mA, 3- or 4-wire, sink or source
Signal output digital
HART® w/ 3- or 4-wire, PROFIBUS® PA, FOUNDATION fieldbus™ H1 and Modbus RTU w/ 4-wire
Temperature
-40 to 65 °C (-40 to 149 °F) without relay
Pressure
20.7 to 38.4 inch Hg / 700 to 1,300 mbar
Transmitter housing
Epoxy coated copper-free aluminium or stainless steel SS316 L
Enclosure protection type
NEMA 4X & 7, IP65/66/67
Cable entry point
3/4” NPT threaded holes or M20 cable gland
Dimensions (H x W x D), approx.
11.0” x 5.9” x 5.1” / 280 × 150 × 130 mm
Weight, approx.
w/o docking station Aluminium 4.9 lbs / 2.2 kg
w/o docking station SS316 L 8.8 lbs / 4.0 kg
The Dräger Polytron® 8700 IR is an advanced explosion proof transmitter for the detection of combustible gases in the lower explosion limit (LEL). It uses a high performance infrared Dräger PIR 7000 sensor, which will quickly detect most common hydrocarbon gases. Besides a 3 wire 4 to 20 mA analog output with relays, it also offers Modbus and Fieldbus making it compatible with most control systems.
• Efficient, stable and robust—the Dräger PIR 7000
• Easy device management via digital communication
• Same design, same operating principle
• Three relays for controlling external equipment
• Safe, robust housing for every application
• Make the impossible possible with the remote sensor
• Data logger
For the detection of combustible gases in the lower explosion limit (LEL). It uses a high performance infrared Dräger PIR 7000 sensor, which will quickly detect most common hydrocarbon gases. Besides a 3 wire 4 to 20 mA analog output with relays, it also offers Modbus and Fieldbus making it compatible with most control systems. The unique 4 beam signal stabilizing system makes the sensor resistant to dust or dirt deposits on the optical surfaces. Environmental and aging effects are compensated ensuring long term, drift free operation.
Type
Explosion proof / flameproof enclosed transmitter (“d”) or combined with increased safety (“d/e”)
Gases
Flammable gases and vapours
Measuring range
0 to 20 … 100 % LEL
Display
Backlit graphic LCD; 3 Status LEDs (green/yellow/red)
Signal output analogue
4 to 20 mA, 3- or 4-wire, sink or source
Signal output digital
HART® w/ 3- or 4-wire, PROFIBUS® PA, FOUNDATION fieldbus™ H1 and Modbus RTU w/ 4-wire
Temperature
-40 to 65 °C (-40 to 149 °F) without relay
Pressure
20.7 to 38.4 inch Hg / 700 to 1,300 mbar
Transmitter housing
Epoxy coated copper-free aluminium or stainless steel SS316 L
Enclosure protection type
NEMA 4X & 7, IP65/66/67
Cable entry point
3/4” NPT threaded holes or M20 cable gland
Dimensions (H x W x D), approx.
11.0” x 5.9” x 5.1” / 280 × 150 × 130 mm
Weight, approx.
w/o docking station Aluminium 4.9 lbs / 2.2 kg
w/o docking station SS316 L 8.8 lbs / 4.0 kg
The Dräger Polytron® 8900 UGLD transmitter is an early warning area monitor for detecting high-pressure gas leaks in outdoor industrial process environments. Thanks to an ultrasonic acoustic sensor, it responds earlier than conventional gas detectors because it registers the sound of leaking gas instead of measuring the concentration of accumulated gas clouds. As gas escapes, leaks are immediately detected in the surrounding area, regardless of the wind direction.
• Ultrasonic sensor technology – the early warning system for gas leaks
• A perfect complement to your gas detection system
• Delivers results that are easy to understand
• Can even detect gas leaks in loud industrial environments
• Robust design and fully-sealed sensor
For detecting high-pressure gas leaks in outdoor industrial process environments. Thanks to an ultrasonic acoustic sensor, it responds earlier than conventional gas detectors because it registers the sound of leaking gas instead of measuring the concentration of accumulated gas clouds. As gas escapes, leaks are immediately detected in the surrounding area, regardless of the wind direction. Environmental influences such as wind can delay or prevent a gas cloud from being detected by gas sensors. On the contrary, the DrägerPolytron 8900 UGLD is not affected by environmental factors and detects a high-pressure gas leak as soon asgas escapes. Effective early gas leak warnings can prevent unnecessary shutdowns, saving time and money.
Type
Explosion proof / flameproof enclosed transmitter (“d”) or combined with increased safety (“d/e”)
Gases
Flammable and toxic gases such as hydrogen, methane, ethylene, propane, CO2, nitrogen and hydrogen sulphide
Measurement ranges
0-100% equivalent to 55-110 dB; typical alarm setting 10% UGLD signal above background
Display
Back-lit graphic LCD display; 3 status LEDs (green/yellow/red)
Sensor Type
PVCC coated piezoelectric microphone with built-in automatic self-test sound generator
Sensor Performance
Response Time < 3 sec Minimum Pressure > 2 bar (29 psi) Methane
Coverage Radius 6.5ft -65 ft depending on gas type, leak rate and background noise
Frequency Range 18 kHz – 80 kHz
Electrical data
Analogue signal output 4 to 20 mA
Digital signal output HART®
Power supply 10 to 30 V DC, 3-wire
The Dräger Polytron® SE Ex … DD sensing heads are gas detectors for the continuous monitoring of flammable gases and vapors in the ambient air. The measurement is based on the heat of reaction principle, where a chemical reaction takes place in a catalytic bead (so-called pellistor) inside the sensor.
• Dräger Polytron SE Ex
• Eight housing variants
• Comprehensive explosion protection
• Measuring signal
• Pellistor sensors type DD
• Environmental conditions
• Poison resistance
• Very short response times
• Measuring function for explosion protection
for the continuous monitoring of flammable gases and vapors in the ambient air. The measurement is based on the heat of reaction principle, where a chemical reaction takes place in a catalytic bead (so-called pellistor) inside the sensor. The sensing heads are intended to be used in the harsh industrial environment and connected to a suitable central controller by means of a 3-core cable.
Type
Sensing head with catalytic bead sensor
Gases and Vapors
Flammable gases and vapors in the ambient air such as methane, propane, acetone, acetylene, ammonia, petrol 065/095, benzene, 1.3-butadiene, n-butane, n-butyl acetate, diethyl ether, dimethyl ether, ethanol, ethylene (ethene), ethyl acetate, ethylene oxide, nhexane, hydrogen, methanol, methyl ethyl ketone (MEK), methyl methacrylate, n-nonane, n-octane, n-pentane, i-propanol, propylene (propene), propylene oxide, toluene and oxylene.
Maximum cable length
between sensing head and controller Polytron SE Ex : 3 x 1.5 mm2: 1450 m
Ambient conditions
atmospheric pressure: 800 … 1100 mbar
Expected sensor lifetime
> 3 years
Dimensions (w x h x d) and weight
Small standard housing 80 x 130 x 56 mm incl. sensor and cable gland, 0.5 kg
Housings
IP 66, glass fiber reinforced Polyester (GRP)
Measuring function (94/9/EC)
Measuring function for explosion protection acc. to EN 60079-29-1 for the a.m. gases and vapors
Cable gland
M 20 x 1.5 – exception: Sensing head Polytron SE Ex PR NPT1 DD (comes without cable gland)
The Draeger Pulsar 7000 Series are stationary open path gas detectors for the detection of explosive hydrocarbons in gases and vapours.
The robust design and the extremely rapid response time make the Draeger Pulsar 7000 Series a dependable solution for your requirements in the oil and gas industry, as well as the chemical industry.
• Reliable and quick measuring
• Reliable even in adverse weather conditions
• Easy to align, configure and commission
• On site diagnostics
• Documented security – protocol and integrated data
• The right model for any job
• Chemical, oil and gas industry
• Fenceline monitoring
• Area monitoring
• Measured at a distance of up to 200 metres within two seconds
Type
Explosion-proof open-path gas detector based on infrared absorption spectroscopy
Gases
Wide range of hydrocarbons, including the alkane series from methane to hexane, propylene
Measuring ranges
Min. 0 to 4 LEL m, max. 0 to 8 LEL m
Gas category
IEC, NIOSH or PTB; selectable
Operating range
4 to 60 m, 30 to 120 m or 100 to 200 m
Signal output
Analogue – 4 to 20 mA , Digital – HART®7
Power consumption
< 5 W receiver, < 9 W transmitter
Operating voltage
18 to 32 VDC (24 VDC nominal)
Response time t90
< 2 s (under normal operating conditions when using the digitallink)
Skew tolerance
+/- 0.6°; +/- 1,6° with Tx S
Temperatur
-40 to + 60 °C, -40 to +140 °F
Pressure
800 to 1,100 hPa
Air humidity
0 to 100% rel. humidity, non-condensing
Material
Stainless steel AISI 316L “Marine Grade”
Protection class
IP66/IP67
Dimensions (W x H x D,approx.)
430 x 670 x 170 mm, incl. cable bend with vertical mounting plate
Weight (approx.)
9 kg (19.84 lbs), each transmitter and receiver incl. backplate and weather shield
Approvals
ATEX / IECEx, DNV GL, SIL 2 SC3 Certification by TÜV Nord (EN 61508),
In many fields of work, quick and reliable gas detection is a must. This is why we offer the Dräger VarioGard® stationary gas detector range. The Dräger VarioGard® 2300 IR monitors possible gas leaks of methane or LPG.
• The one to count on
• Simple set-up and handling
• Gas library and variable measuring ranges
• Standardised output signal
The Dräger VarioGard 2300 comes equipped with highly precise infrared optical sensors, which greatly reduce the possibility of false alarms so that it should only sound when real danger is evident. The IR sensors are also extremely robust and rarely need to be recalibrated.
Type
Transmitter for the measurement of concentrations of gases in the ambient air
Gases and measuring ranges
CH4 : 0 to 100 % LEL
LPG : 0 to 100 % LEL
Display
2-colour LED (green, yellow): operation, maintenance
In many fields of work, quick and reliable gas detection is a must. This is why we offer the Dräger VarioGard® stationary gas detector range. Dräger VarioGard® 2320 IR monitors possible gas leaks or work place exposure limits of carbon dioxide.
• The one to count on
• Simple set-up and handling
• Gas library and variable measuring ranges
• Standardised output signal
The Dräger VarioGard 2320 comes equipped with highly precise infrared optical sensors, which greatly reduce the possibility of false alarms so that it should only sound when real danger is evident. The IR sensors are also extremely robust and rarely need to be recalibrated.
Type
Transmitter for the measurement of concentrations of gases in the ambient air
Gases and measuring ranges
CO2 – 0 to 5 Vol.-%
Display
2-colour LED (green, yellow): operation, maintenance