Dräger REGARD® 2400 and 2410 are flexible small control units for detection of toxic gases and oxygen as well as combustible gases and vapours. Combined with the Dräger transmitters or sensing heads Dräger REGARD® 2400 or 2410 forms a low-maintenance gas detection system for reliable protection.
• Versions and configuration
• Easy to operate
• Flexible extensions
For detection of toxic gases and oxygen as well as combustible gases and vapours. Combined with the Dräger transmitters or sensing heads Dräger REGARD® 2400 or 2410 forms a low-maintenance gas detection system for reliable protection. The REGARD 2400 comes with an enclosure with integral power supply unit and can be mounted directly to a wall. The REGARD 2410 has been designed for economical mounting on DIN rails in existing switch or wall cabinets.
Central unit
Independent 4-channel wall-mounted (2400) or rail-mounted (2410) control unit in accordance with DIN EN 50022
Power supply
24 VDC / 110 to 230 VAC 50 to 60 Hz (2400)
Inputs
2-wire/3-wire 4 to 20 mA transmitter or Dräger Polytron SE Ex sensing heads via signal converter (optional)
Outputs
Potential-free relay contacts of the 2 gas alarm relays plus one acoustic alarm relay and one failure relay each for 250 VAC, 2 A (2400 DPCO and 2410 SPCO)
The devices of the Draeger REGARD 3900 series can be used as standalone controllers. You can configure up to 16 measuring channels. In addition, the modular setup enables you to customise the control units to the demands of your plant. You can also embed further features to existing alarms.
• Input modules
• Relay module
• Output module (Repeater module)
• Configure your control unit quickly
• Mounting and installation
• Gateway solution
applications
Type
Control unit for location in a non-hazardous area
Inputs
all configuration via PC or laptop
4 to 20 mA transmitter with 2- or 3-core cable
Outputs
Alarm 1, Alarm 2 and Fault as standard
Warning and inhibit relays on optional relay module
Single, common or voted alarms on optional relay module
Acknowledgeable relays on optional relay module
The Draeger REGARD 7000 is a modular and therefore highly expandable analysis system for monitoring various gases and vapours. Suitable for gas warning systems with various levels of complexity and numbers of transmitters, the Draeger REGARD 7000 also features exceptional reliability and efficiency. An additional benefit is the backward compatibility with the REGARD.
• Individual and highly compatible
• Safe and secure with minimal false alarms
• Optimal installation and configuration
• Maintenance and documentation — as efficient as possible
applications
Temperature
0 to 55 °C / 32 to 131 °F
Humidity
5 to 95% RH, non-condensing
Pressure
700 to 1,300 hPa
Height
2,000 m to 3,000 m
System reaction times
1 s to 3.3 s
Operating voltage
24 V (19.2 to 28.8 V) DC
Current draw
Typ. 1.0 A at 24 V DC
Dimensions
266 x 483 x 68 mm / 10.47 x 19.02 x 2.68″ (H x W x D)
In many fields of work, quick and reliable gas detection is a must. This is why we offer the Dräger VarioGard® stationary gas detector range. The Dräger VarioGard® 2300 IR monitors possible gas leaks of methane or LPG.
• The one to count on
• Simple set-up and handling
• Gas library and variable measuring ranges
• Standardised output signal
The Dräger VarioGard 2300 comes equipped with highly precise infrared optical sensors, which greatly reduce the possibility of false alarms so that it should only sound when real danger is evident. The IR sensors are also extremely robust and rarely need to be recalibrated.
Type
Transmitter for the measurement of concentrations of gases in the ambient air
Gases and measuring ranges
CH4 : 0 to 100 % LEL
LPG : 0 to 100 % LEL
Display
2-colour LED (green, yellow): operation, maintenance
In many fields of work, quick and reliable gas detection is a must. This is why we offer the Dräger VarioGard® stationary gas detector range. Dräger VarioGard® 2320 IR monitors possible gas leaks or work place exposure limits of carbon dioxide.
• The one to count on
• Simple set-up and handling
• Gas library and variable measuring ranges
• Standardised output signal
The Dräger VarioGard 2320 comes equipped with highly precise infrared optical sensors, which greatly reduce the possibility of false alarms so that it should only sound when real danger is evident. The IR sensors are also extremely robust and rarely need to be recalibrated.
Type
Transmitter for the measurement of concentrations of gases in the ambient air
Gases and measuring ranges
CO2 – 0 to 5 Vol.-%
Display
2-colour LED (green, yellow): operation, maintenance
The Dräger VarioGard® Central Unit is at the center of a cost-efficient, modular gas detection system. A digital Bus makes it possible to connect and manage up to 100 transmitters for various gases.
A VarioGard system can be individually put together and programmed, in accordance with customer specifications. VarioGard Transmitter, VarioGard Relay Module, VarioGard Converter Module and VarioGard Battery Module can be selected as modules. The three-wire digital bus cable for connecting the individual modules can be up to 1100m long.
Type
Control unit for a Dräger VarioGard® system
Display
LCD; 2 lines, 20 characters; for concentrations, alarms and menu
Status indicator
3-colour LED; operation, alarm, service
Inputs
6 function keys
Alarm output
Internal horn, red status LED, LCD and alarm relay
Outputs
5 configurable, potential-free, normally-open relays for alarms and faults
Electrical connections
Power connection, relay outputs, system bus line, battery module, remote acknowledgement terminal, PC port
Temperature
-20 to 40°C
Humidity
10 to 95% rel. hum., non-condensing
Druck
700 to 1,300 hPa
Housing
Plastic ABS, light grey RAL 7035, IP65
M25 x 1.5 mains power connection
M20 x 1.5 (other)