The Draeger REGARD 7000 is a modular and therefore highly expandable analysis system for monitoring various gases and vapours. Suitable for gas warning systems with various levels of complexity and numbers of transmitters, the Draeger REGARD 7000 also features exceptional reliability and efficiency. An additional benefit is the backward compatibility with the REGARD.
• Individual and highly compatible
• Safe and secure with minimal false alarms
• Optimal installation and configuration
• Maintenance and documentation — as efficient as possible
applications
Temperature
0 to 55 °C / 32 to 131 °F
Humidity
5 to 95% RH, non-condensing
Pressure
700 to 1,300 hPa
Height
2,000 m to 3,000 m
System reaction times
1 s to 3.3 s
Operating voltage
24 V (19.2 to 28.8 V) DC
Current draw
Typ. 1.0 A at 24 V DC
Dimensions
266 x 483 x 68 mm / 10.47 x 19.02 x 2.68″ (H x W x D)
Accurate and rapid gas detection is critical in numerous industries. The Dräger VarioGard® stationary gas detector series meets this need, with the Dräger VarioGard® 2300 IR tailored for detecting potential methane or LPG gas leaks.
• The one to count on
• Simple set-up and handling
• Gas library and variable measuring ranges
• Standardised output signal
The Dräger VarioGard 2300 comes equipped with highly precise infrared optical sensors, which greatly reduce the possibility of false alarms so that it should only sound when real danger is evident. The IR sensors are also extremely robust and rarely need to be recalibrated.
Type
Transmitter for the measurement of concentrations of gases in the ambient air
Gases and measuring ranges
CH4 : 0 to 100 % LEL
LPG : 0 to 100 % LEL
Display
2-colour LED (green, yellow): operation, maintenance
Fast and accurate gas detection is vital across various industries.The Dräger VarioGard® stationary gas detector series meets this need, with the Dräger VarioGard® 2300 IR tailored for detecting potential methane or LPG gas leaks.
• The one to count on
• Simple set-up and handling
• Gas library and variable measuring ranges
• Standardised output signal
The Dräger VarioGard 2320 comes equipped with highly precise infrared optical sensors, which greatly reduce the possibility of false alarms so that it should only sound when real danger is evident. The IR sensors are also extremely robust and rarely need to be recalibrated.
Type
Transmitter for the measurement of concentrations of gases in the ambient air
Gases and measuring ranges
CO2 – 0 to 5 Vol.-%
Display
2-colour LED (green, yellow): operation, maintenance
The Dräger VarioGard® Central Unit is at the center of a cost-efficient, modular gas detection system. A digital Bus makes it possible to connect and manage up to 100 transmitters for various gases.
A VarioGard system can be individually put together and programmed, in accordance with customer specifications. VarioGard Transmitter, VarioGard Relay Module, VarioGard Converter Module and VarioGard Battery Module can be selected as modules. The three-wire digital bus cable for connecting the individual modules can be up to 1100m long.
Type
Control unit for a Dräger VarioGard® system
Display
LCD; 2 lines, 20 characters; for concentrations, alarms and menu
Status indicator
3-colour LED; operation, alarm, service
Inputs
6 function keys
Alarm output
Internal horn, red status LED, LCD and alarm relay
Outputs
5 configurable, potential-free, normally-open relays for alarms and faults
Electrical connections
Power connection, relay outputs, system bus line, battery module, remote acknowledgement terminal, PC port
Temperature
-20 to 40°C
Humidity
10 to 95% rel. hum., non-condensing
Druck
700 to 1,300 hPa
Housing
Plastic ABS, light grey RAL 7035, IP65
M25 x 1.5 mains power connection
M20 x 1.5 (other)
The Dräger Flame 1350 combines UV and IR sensors to detect hydrocarbon-based fires. These powerful sensors and complex algorithms provide increased safety and fewer false alarms.
• Fast and safe detection
• Prevention of false alarms
• Robust and durable
• Simple verification
• Maximum flexibility
The Dräger Flame 1500 flame detector uses its triple IR sensor to detect hydrocarbon fires even at great distances. It offers you high reliability against false alarms.
• Fast and reliable flame detection
• Prevention of false alarms
• Robust and resistant
• Simple check
With its triple IR sensor, the Dräger Flame 1750 H2 detects hydrogen-based fires. It offers you high reliability against false alarms and its good measurement performance remains even at extreme temperatures
• Fast and safe detection
• Developed for hydrogen
• Robust and durable
• Simple verification